Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli ... [et al.]

It is well known that the internal partial discharge (PD) are small electric sparks that occurred due to defect in power cable insulation. This will be lead to premature failure of cable which consequently interrupt the supply on the distribution lines. In this paper, the results of internal partial...

Full description

Saved in:
Bibliographic Details
Main Authors: Rameli, Norhidayu (Author), Abd. Halim, Huzainie Shafi (Author), Nor Azli, Muhd. Irfan (Author), Anthony, Tashia Marie (Author), Pangah @ Pa'at, Mohd Azraei (Author), Ibrahim, Muhammad Faiz (Author), Nor Arifin, Nur Amira (Author)
Format: Book
Published: Universiti Teknologi MARA Press (Penerbit UiTM), 2020.
Subjects:
Online Access:Link Metadata
Tags: Add Tag
No Tags, Be the first to tag this record!

MARC

LEADER 00000 am a22000003u 4500
001 repouitm_42390
042 |a dc 
100 1 0 |a Rameli, Norhidayu  |e author 
700 1 0 |a Abd. Halim, Huzainie Shafi  |e author 
700 1 0 |a Nor Azli, Muhd. Irfan  |e author 
700 1 0 |a Anthony, Tashia Marie  |e author 
700 1 0 |a Pangah @ Pa'at, Mohd Azraei  |e author 
700 1 0 |a Ibrahim, Muhammad Faiz  |e author 
700 1 0 |a Nor Arifin, Nur Amira  |e author 
245 0 0 |a Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli ... [et al.] 
260 |b Universiti Teknologi MARA Press (Penerbit UiTM),   |c 2020. 
500 |a https://ir.uitm.edu.my/id/eprint/42390/1/42390.pdf 
500 |a  Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli ... [et al.]. (2020) Journal of Electrical and Electronic Systems Research (JEESR) <https://ir.uitm.edu.my/view/publication/Journal_of_Electrical_and_Electronic_Systems_Research_=28JEESR=29/>, 17. pp. 95-100. ISSN 1985-5389  
520 |a It is well known that the internal partial discharge (PD) are small electric sparks that occurred due to defect in power cable insulation. This will be lead to premature failure of cable which consequently interrupt the supply on the distribution lines. In this paper, the results of internal partial discharge detected by rogowski coil (RC) sensor were presented. The RC sensors were designed, fabricated and tested in the laboratory with varying high frequency sinusoidal and impulse signals. An artificial PD defect was also created inside a straight through joint (STJ), medium voltage aerial bundle cable (MVABC) to generate PD signals. PD testing data in the laboratory were collected and analysed. Results indicates that the RC sensors able to detects injected continuos sinusoidal signal at lower frequencies ranging from 0.5 MHz to 10 MHz. The detected PD signal generated from artificial PD defect from RC sensor were found to be slightly higher amplitude as compared to commercial PD sensor, High Frequency Current Transformer (HFCT). Thus findings shows that the RC sensor able to be used as sensor to detect the internal partial discharge at MVABC specifically at STJs. 
546 |a en 
690 |a Detectors. Sensors. Sensor networks 
655 7 |a Article  |2 local 
655 7 |a PeerReviewed  |2 local 
787 0 |n https://ir.uitm.edu.my/id/eprint/42390/ 
787 0 |n https://jeesr.uitm.edu.my 
787 0 |n https://doi.org/10.24191/jeesr.v17i1.013 
856 4 1 |u https://ir.uitm.edu.my/id/eprint/42390/  |z Link Metadata